Modbus RTU Soft Starter 380V 7.5–280 kW — CMC-MX Series with Built-in Bypass

3-phase, AC380V ±15%
VOLTAGE & PHASE
18A–560A
CURRENT
Current Limit / Voltage Ramp Start, Soft Stop
CONTROL
7.5–280 kW
POWER
Thermal Overload (Class 10A–30)
OVERLOAD
Modbus-RTU (RS485)
COMMUNICATION

Brief Overview

The CMC-MX is a compact 3-phase 380 V soft starter for squirrel cage asynchronous motors from 7.5 kW to 280 kW (18 A to 560 A, 18 ratings), with the bypass contactor and the current transformer built into the enclosure. Because the bypass is internal, no external contactor has to be wired and no external CTs have to be fitted — the panel is smaller, the wiring is shorter and the cost of the starting panel is lower.Starting is done either by current limiting or by voltage ramp, and a programmable step (kick) start can be applied in both modes to break the static friction of high-torque loads. Stopping can be free or soft, with a settable soft stop time and soft stop termination voltage.Protection covers phase failure, overcurrent, short circuit, SCR protection, overheat, phase current imbalance, leakage, underload and internal contactor faults, together with an electronic thermal overload whose trip curve can be set to 10A, 15, 20, 25 or 30 level. A 4-digit display and keypad handle setup and fault diagnosis, and seven historical faults are stored in the parameters.The CMC-MX communicates over Modbus-RTU (RS485) with up to 32 units on one bus, provides a 4–20 mA analog output, and its mains frequency of 50 or 60 Hz is set by parameter — one unit suits either grid.

Certifications

ISO
18-month warranty Lead time 7–15 days OEM / ODM

Key Features of the CMC-MX Modbus RTU Soft Starter with Built-in Bypass

Internal bypass contactor and current transformer — nothing external to wire

The CMC-MX is a Modbus RTU soft starter for 3-phase 380 V … integrated inside the enclosure. When the motor reaches full speed the internal bypass contactor closes and the thyristors are taken out of circuit, so the starter does not need an external bypass contactor, external CTs, or the panel space and wiring that come with them. For panel builders who standardise on low voltage soft starters for general industrial loads, this is the difference between a two-component starting section and a single device: fewer terminals, shorter busbars, less heat inside the cabinet and a shorter assembly time.

Current limiting start, voltage ramp start and programmable kick start

Two starting modes are available and a programmable step (kick) start can be applied in either of them, so the starting curve can be matched to the load instead of the other way round:

  • Current limiting soft start — the output voltage rises until the output current reaches the set limit (parameter C005, 150–500 % of motor rated current, factory 350 %). The current is then held at that value while the motor accelerates and the voltage is raised to full value. This is the mode to use where the supply capacity is limited or the network must not see a heavy inrush.
  • Voltage ramp start — the voltage rises from the initial value (C003, 25–100 % Ue, factory 30 %) to full voltage over the ramp time (C004, 0–60 s, factory 10 s). It is intended for high-inertia loads, where it reduces the starting impact and the mechanical stress on the drive train.
  • Step torque (kick) start — an instantaneous high starting torque is applied for a settable step time (C001 step voltage, C002 step time) to overcome large static friction, after which the motor continues on the normal initial-voltage-and-ramp curve. Loads such as crushers, mixers and screw compressors need this kick to break away.

Free stop and soft stop

With the soft stop time (C007) set to zero the starter stops in free stop mode: the bypass contactor control relay is blocked and the thyristor output is blocked immediately, so the motor coasts down on the inertia of the load. With a soft stop time set, the starter disconnects the bypass contactor first and then reduces the output voltage to the soft stop termination voltage (C008, 25–60 %) within the soft stop time before switching to free stop — the mode to use wherever the driven machine has to be brought down under control rather than by inertia.

Motor protection with a selectable electronic overload curve

Both the motor and the starter are protected against the faults that actually occur in service:

  • phase failure (input and output)
  • overcurrent and overcurrent duration (C101, C102)
  • short circuit and thyristor (SCR) protection
  • overheat protection
  • phase current imbalance and its delay time (C103, C104)
  • leakage detection
  • electronic thermal overload with a selectable trip curve — 10A, 15, 20, 25 or 30 level (C105)
  • internal contactor fault
  • underload protection, which can be switched off by setting C111 to 100

The motor rated current is entered in C100, and it must not be set below 50 % of the rated current of the controller. When a protection operates, the corresponding fault type is shown on the display for fast diagnosis, and the last seven faults are kept in the parameters C310 to C316.

Modbus-RTU over RS485 — up to 32 starters on one bus

The CMC-MX has an RS485 port with Modbus-RTU protocol. Up to 32 units can be connected on one network, with communication addresses from 1 to 32 (factory default 1) and baud rates of 2400, 4800, 9600 or 19200 bps (factory default 9600). Start, stop, parameter read and write and status monitoring are all available over the bus, and standard Modbus frames with CRC checking are used, so the starter can be dropped into an existing PLC or SCADA network without a gateway. The full register map is listed further down this page.

4–20 mA analog output

An analog output (terminals X1/1 AO− and X1/2 AO+) delivers 4–20 mA into a load of 150–500 ohm for remote indication. Parameter C208 selects average current 1 (0–200 % Ie) or average current 2 (0–400 % Ie), so the signal can be scaled to the range the control system expects.

50 / 60 Hz selected by parameter

The power frequency is set in the parameters, so the same CMC-MX covers 50 Hz and 60 Hz networks. For an export project the destination grid does not change the part number, and a machine built for one market can be re-used in another with a setting change.

4-digit display, keypad and fault memory

A 4-digit LED display with a keypad monitors the working condition of the equipment and gives rapid fault diagnosis on site. Setup is done from the same keypad, with parameters grouped into start and stop control (C000–C016), motor protection (C100–C116), port setting (C200–C216) and recording (C300–C316).

Technical Specifications

Applicable motorOrdinary squirrel cage AC asynchronous (induction) motor
Power range7.5 – 280 kW
Rated current18 – 560 A, 18 ratings in total
Mains voltage, standard wiring3-phase AC 380 V ±15 %
Mains voltage, internal delta wiring3-phase AC 380 V ±30 %
Control supplyAC 110 – 220 V ±15 %, 50 / 60 Hz
Start ramp modeCurrent limiting start, voltage ramp start, programmable step (kick) start
Stop modeFree stop, soft stop
Current limiting factor150 – 500 % Ie (factory 350 %)
Initial voltage25 – 100 % Ue (factory 30 %)
Ramp time0 – 60 s (factory 10 s)
Soft stop time0 – 60 s
Soft stop termination voltage25 – 60 % (factory 25 %)
Starting frequencyFrequent or infrequent starts; no more than 10 starts per hour recommended
Logic inputImpedance 1.8 kohm, power supply +24 V
Analog output4 – 20 mA, load impedance 150 – 500 ohm
Protection functionsPhase failure, overcurrent, short circuit, SCR (thyristor) protection, overheat, phase current imbalance, leakage detection, electronic thermal overload, internal contactor fault, underload, wiring and inner fault
Electronic overload curveSelectable 10A / 15 / 20 / 25 / 30 level
CommunicationModbus-RTU, RS485; up to 32 units; 2400 – 19200 bps
Setting and display4-digit LED display with keypad; 7 historical faults stored (C310 – C316)
Degree of protectionIP00, IP20
CoolingNatural cooling or forced air cooling
InstallationWall mounted, vertical installation
StandardGB/T 14048.6-2016
Ambient conditionsAltitude up to 2 000 m without derating, above 2 000 m derate for use; ambient temperature −25 to +45 °C; relative humidity below 95 % (20 ± 5 °C); indoor installation with good ventilation, free of flammable, explosive or corrosive gas and conductive dust; vibration below 0.5 G

Standard wiring means the motor winding is connected in delta or star and the thyristors sit between the supply and the motor. In internal delta wiring the thyristors sit in series with each motor winding, so the current through the starter is 1/1.732 (about 58 %) of the line current — see the internal delta section below.

Model Selection: 18 Models from 7.5 kW to 280 kW

ModelRated currentMotor powerRecommended cable, standard wiringSize W x H x T (mm)Net weight
CMC-008/3-MX18 A7.5 kW6 mm² copper173 x 275 x 1925.6 kg
CMC-011/3-MX24 A11 kW10 mm² copper
CMC-015/3-MX30 A15 kW16 mm² copper
CMC-018/3-MX39 A18.5 kW16 mm² copper
CMC-022/3-MX45 A22 kW16 mm² copper
CMC-030/3-MX60 A30 kW25 mm² copper
CMC-037/3-MX76 A37 kW25 mm² copper
CMC-045/3-MX90 A45 kW35 mm² copper
CMC-055/3-MX110 A55 kW50 mm² copper
CMC-075/3-MX150 A75 kW70 mm² copper
CMC-090/3-MX180 A90 kW20 x 3 copper bar285 x 450 x 30525.1 kg
CMC-110/3-MX218 A110 kW20 x 3 copper bar
CMC-132/3-MX260 A132 kW25 x 3 copper bar
CMC-160/3-MX320 A160 kW30 x 3 copper bar
CMC-185/3-MX370 A185 kW30 x 4 copper bar
CMC-220/3-MX440 A220 kW40 x 5 copper bar320 x 523 x 33034.5 kg
CMC-250/3-MX500 A250 kW40 x 5 copper bar
CMC-280/3-MX560 A280 kWAsk us for the internal delta cable schedule

Model code: CMC-★★★/3-MX — ★★★ is the applicable motor power code, 3 is the mains voltage class (380 V) and MX is the built-in bypass series. Cable sizes are the standard wiring values from the CMC-MX manual for 380 V; cable size and breaker rating should always be checked against the actual motor current, cable length, installation method and local code.

Motors larger than 280 kW are covered by the CMC-LX built-in bypass soft starter series (7.5 – 630 kW), which uses the same internal bypass concept in a larger frame and is compared with the CMC-MX further down this page.

Internal Delta (Inside-Delta) Wiring

What changes with inside-delta wiring

In standard wiring the thyristors of the soft starter are connected between the supply and the motor, and they carry the full line current. In internal delta wiring the motor winding is connected in delta and the thyristors are placed in series with each winding, so the current that flows through the starter — and through each winding — is 1/1.732 of the line current, about 58 %. The main advantage of the internal triangular control is that the soft starter can be derated: a smaller rating can be selected for the same motor, which reduces both cost and panel size. The mains voltage tolerance in this mode is AC 380 V ±30 %.

When to use it

Internal delta wiring is worth considering for high-power, high-inertia drives where the starting current is the constraint and the cost of the starter is a large part of the panel, and where the motor has six terminals available for delta connection. Standard wiring remains the simpler choice for small motors and for retrofits where the existing motor is already star-connected or has only three terminals brought out. Tell us the motor nameplate data, the starting duty and the wiring method, and we will confirm the correct model and cable schedule.

Terminal Description

TerminalNameDescription
1L1, 3L2, 5L3AC power inputConnected to the three-phase AC power supply (main circuit)
2T1, 4T2, 6T3Soft start outputConnected to the three-phase asynchronous motor (main circuit)
X1/1Analog output AO−4 – 20 mA
X1/2Analog output AO+Output load impedance 150 – 500 ohm
X1/3COMCommon port
X1/4External control start (RUN)Start when X1/4 and X1/3 are short-circuited
X1/5External control stop (STOP)Stop when X1/5 and X1/3 are disconnected
X1/6Programmable digital port D1Fault clear input or emergency stop input, selected by C201
X2/1RS485 ground (GND)RS485 communication, GND single point grounding
X2/2RS485+ (A)Modbus-RTU communication
X2/3RS485− (B)Modbus-RTU communication
X3/1, X3/2Interlocking control relay K1Passive normally open, AC 250 V / 5 A, DC 30 V / 5 A
X3/3, X3/4Fault output relay K2Passive normally open, AC 250 V / 5 A, DC 30 V / 5 A; operates in case of fault
X3/5, X3/6Programmable output relay K3Passive normally open AC 250 V / 5 A, DC 30 V / 5 A; function defined by C202
X3/7PEProtective earth
X3/8, X3/9Control power supply L / NAC 110 V – AC 220 V ±15 %, 50 / 60 Hz

For the basic single-node passive control scheme the start and stop contacts are wired to X1/4, X1/5 and X1/3. A passive double-node scheme is also possible, in which RUN and STOP are inching signals; in that scheme the start and stop commands are also valid from the panel.

Key Setting Parameters

ParameterNameSetting rangeFactory value
C000Starting mode / start ramp mode0 – 10
C001Step voltage25 – 100 % Ue20 %
C002Step time0 – 200 x 10 ms0
C003Initial voltage25 – 100 % Ue30 %
C004Ramp time0 – 60 s10 s
C005Current limiting factor150 – 500 % Ie350 %
C007Soft stop time0 – 60 s0
C008Soft stop termination voltage25 – 60 %25 %
C200Selection of control0 keyboard, 1 communication, 2 keyboard and communication0
C201D1 port input mode0 fault clear input, 1 emergency stop input0
C202Programmable relay output mode0 full voltage output, 1 starting process, 2 soft stop process, 3 fault output1
C203Relay output delay0 – 250 s0
C204Communication address1 – 321
C205Communication baud rate2400 / 4800 / 9600 / 19200 bps9600
C208Analog output mode0 average current 1 (0 – 200 % Ie), 1 average current 2 (0 – 400 % Ie)0

Motor protection is set in the C100 group: C100 motor rated current, C101 overcurrent protection value, C102 overcurrent duration, C103 phase current imbalance, C104 imbalance delay, C105 electronic thermal overload level and tripping time, C106 SCR protection option, C107 phase sequence detection, C111 and C112 underload protection. C111 set to 100 disables the underload function.

Modbus-RTU Communication and Register Map

The CMC-MX uses Modbus-RTU over RS485. Up to 32 starters can share one bus with addresses 1 to 32 (factory 1), and the baud rate is set in C205 to 2400, 4800, 9600 or 19200 bps (factory 9600). Transmission uses the standard RTU frame with a silent interval of at least 3.5 characters between frames: slave address, function code, data and a CRC check word, each byte sent as two hexadecimal characters. The registers below are all 16-bit unsigned integers and are readable and writable.

Register (dec)FunctionTypeAccess
0000Starting modeUintR / W
0001Step voltageUintR / W
0002Step timeUintR / W
0003Initial voltageUintR / W
0004Ramp timeUintR / W
0005Current limiting factorUintR / W
0006Second starting allowedUintR / W
0007Soft stop timeUintR / W
0008Soft stop termination voltageUintR / W
0009Starting time delayUintR / W
0010Secondary current limiting factorUintR / W
0017Motor rated currentUintR / W
0018Overcurrent protectionUintR / W
0019Overcurrent durationUintR / W
0020Phase current imbalanceUintR / W
0021Phase current imbalance delayUintR / W
0022Electronic thermal overloadUintR / W
0023SCR protection optionUintR / W
0024Phase sequence detectionUintR / W
0025Frequency protection settingUintR / W
0026Starting time limitUintR / W
0027Motor wiring settingUintR / W
0028Current underload setting during operationUintR / W
0029Current underload delay output timeUintR / W
0034Selection of controlUintR / W
0035D1 port input modeUintR / W
0036Relay output modeUintR / W
0037Relay output delayUintR / W

Typical Applications and Recommended Settings

The CMC-MX is used on the general industrial loads that make up most soft starter demand: pumps, fans, compressors, conveyors, mixers, crushers, hoists and escalators. The table below gives the starting settings recommended by the manufacturer for the most common load types, as a starting point for commissioning.

Load typeInitial voltage (%)Start ramp time (s)Stop ramp time (s)Current limit ILIM
Foreship propeller251002.5
Centrifugal fan252003.5
Centrifugal pump25663
Piston compressor251503
Hoisting machinery301563.5
Mixer401503.5
Crusher301563.5
Screw compressor201503.5
Spiral conveyor belt251063.5
No-load motor251002.5
Conveyor belt2515103.5
Heat pump251563
Escalator251003
Air pump251002.5

Recommended settings from the CMC-MX manual, for reference only. ILIM is the current limiting factor, the same quantity that is set in C005 (150–500 % Ie). Final settings should be confirmed on site during commissioning, with the actual load, supply and starting duty.

CMC-MX, CMC-LX or CMC-HX — Which Series Fits Your Motor

Brigoind supplies the three XICHI low voltage soft starter families that cover most industrial starting duties, so the right frame can be chosen without changing supplier:

  • Built-in bypass soft starter (CMC-LX, 7.5–630 kW) — built-in bypass contactor and current transformer in a larger frame, for motors above the CMC-MX range and for projects that want one series across a whole plant.
  • CMC-HX series, up to 710 kW — the high power option for large pumps, fans, compressors and crushers.
  • CMC-MX series, 7.5 – 280 kW — this page. The most compact and economical of the three, for machines and panels where space is tight.

If you are not sure which series matches your motor, send us the motor nameplate (power, current, voltage, speed), the load type and the starting duty, and we will size it for you. A wider overview of the drive range is on our industrial drives overview page.

FAQ

Does the CMC-MX need an external bypass contactor or current transformer?

No. Both are built into the enclosure, so the starting section only needs the soft starter itself plus a breaker or fuses on the supply side. This is the main difference from a standard soft starter, and it is why a CMC-MX panel is smaller, cooler and faster to wire.

Should I use current limiting start or voltage ramp start?

Use current limiting start where the supply capacity is limited or the network must not see a heavy inrush: the current is held at the set limit (factory 350 % Ie) while the motor accelerates. Use voltage ramp start for high-inertia loads, where the smooth voltage rise matters more than the current ceiling. A programmable kick start can be added to either mode for loads with a high breakaway torque, such as crushers, mixers and screw compressors.

What protections are included?

Phase failure, overcurrent and overcurrent duration, short circuit and thyristor (SCR) protection, overheat, phase current imbalance, leakage detection, electronic thermal overload with a selectable 10A / 15 / 20 / 25 / 30 trip curve, internal contactor fault and underload protection, which can be disabled by setting C111 to 100. The last seven faults are stored in the parameters C310 to C316 for later reading.

How many CMC-MX units can be connected on one RS485 network?

Up to 32. Communication addresses run from 1 to 32 (factory default 1) and the baud rate is set to 2400, 4800, 9600 or 19200 bps (factory default 9600). Standard Modbus-RTU frames with CRC checking are used, so the starter connects directly to a PLC or SCADA system.

Is the CMC-MX a 50 Hz or a 60 Hz product?

Both. The power frequency is selected by parameter, so the same unit works on 50 Hz and 60 Hz networks. For export projects this means the destination grid does not change the part number.

What cable size do I need?

For standard wiring from the 7.5 kW model upwards the recommended primary conductor is 6 mm² copper, rising through 16 mm² at 15 kW, 25 mm² at 30 kW, 50 mm² at 55 kW and 70 mm² at 75 kW, after which copper bar is used — from 20 x 3 at 90 kW to 40 x 5 at 250 kW. The full list is in the model selection table above. With internal delta wiring the current through the starter is only about 58 % of the line current, so the cable and the starter rating can usually be reduced; ask us for the schedule for your motor.

Can I use the CMC-MX above 280 kW?

No. The CMC-MX covers 7.5 – 280 kW (18 – 560 A) in 18 models. Above that, step up to the CMC-LX series (7.5 – 630 kW), which uses the same internal bypass arrangement, or to the CMC-HX series for the largest motors. The series comparison above tells you which one matches your motor.

What is supplied with each starter?

Every unit is shipped with the user manual, the product qualification certificate and the standard mounting parts. Dimensional drawings, the terminal diagram and the parameter list are available on request in English, and we can prepare a cable and breaker schedule for your specific motor and wiring method on request.

Request a Quotation

Send us the motor power, rated current, supply voltage and the load type, and tell us whether you will use standard wiring or internal delta wiring. We will come back with the right CMC-MX model (or the CMC-LX / CMC-HX alternative if your motor is outside the CMC-MX range), a cable and breaker recommendation, and a written quotation.

As a long-term XICHI distributor, we confirm the model against your motor nameplate and starting duty before the order is placed. Request a CMC-MX soft starter quotation — see our soft starter projects or read more about Brigoind.

Dimensional Drawings

Power RangeGHIKLMEDA/B/C
8 ~ 55 kW1732751921332507908650
75 ~ 160 kW285450305230390917015850
185 ~ 280 kW320523330270415919515850

Solutions Across Every Major Industry

From water treatment to data centers — our drives and power solutions keep critical operations running.

Water & Wastewater

Pump speed control, energy savings and smooth starts for treatment plants.

HVAC & Building

Fan and pump control for air handling, cooling towers and building automation.

Oil, Gas & Mining

Heavy-duty drives for conveyors, crushers and pumps in harsh environments.

General Industry

Conveyors, extruders, mixers and machine tools — reliable speed control.

Textile & Printing

Precision tension and speed control for looms, dyeing lines and printing presses.

Food & Beverage

Hygienic drive solutions for conveyors, pumps and packaging lines.

Cement & Minerals

High-torque drives for crushers, mills, fans and heavy conveyor systems.

Marine & Data Center

Marine-grade drives and reliable power for UPS, cooling and server farms.