The XST260 smart soft starter reports faults as E-codes on the LED display, with the fault name shown on the LCD. Seventeen codes are defined in the official table. On this series the most common trips are supply phase loss, machine overheating caused by poor airflow or frequent starting, and an overload that shows up as E05 or E06.

17 codes
CodeFaultCauseWhat to do
E01Main power supply out of phase 主电源缺相One phase of the incoming three-phase supply is missing during start or while running.Check that the three-phase supply is present and reliable at the input terminals.
E02Machine overheating 机器过热The heatsink temperature has exceeded its limit, normally from poor ventilation, a blocked radiator, a start frequency that is too high, or a control supply that sags during start.Confirm the starter is mounted vertically with clear airflow. Check the cooling fan and radiator. Reduce the start frequency. Measure the control power supply voltage under load.
E03Starting timeout 起动超时The motor did not complete the start within the allowed ramp time, usually because the parameter set does not match the motor, or the current limit is too low.Review each working parameter against the motor nameplate. If the start fails repeatedly, raise the current limiting multiple.
E04SCR short circuit or open motor circuit 晶闸管短路或电机回路开路Either a thyristor is short-circuited, the output has lost a phase, the internal connection is wrong, or the motor circuit is open.Check whether the thyristor is damaged, whether the input and output are missing a phase, and whether the contactor is operating. Verify the motor is correctly and reliably connected and not open-circuited internally.
E05Motor running overcurrent 运行过流The load is drawing more current than the set limit while running.Check whether the three-phase voltage is too low, which reduces motor output. Check the driven load for mechanical overload.
E06Electronic thermal overload 电子热过载The running current has stayed above the motor rated current long enough for the thermal model to trip.Check for sustained overload. Confirm the motor rated current parameter matches the nameplate.
E07Phase sequence error 相序错误The incoming line phase order is reversed.Check the incoming phase sequence is A-B-C. Swap two phases if it is not.
E08Phase current imbalance 相电流不平衡The current difference between two phases exceeds the set value.Use a clamp meter to measure each phase current and confirm they are balanced.
E10Parameter loss 参数丢失EEPROM damage has erased the stored parameter set.If the code returns after re-powering, contact the manufacturer. Do not keep re-entering parameters on a damaged EEPROM.
E11Wiring error 接线错误Incorrect wiring in the inner-triangle (delta inside) mode.Compare the actual wiring against the wiring diagram and check the related parameters.
E12Memory failure 存储器故障Abnormal internal storage response.Cycle the control power once. If the code persists, contact the manufacturer.
E13Current underload 电流欠载The running current has dropped below the underload lower limit.Check whether the load has dropped out of the power system, for example a broken belt, a dry pump, or a disconnected coupling.
E14Blocked rotation 堵转The current exceeds the stall current setting.Check whether the motor or driven machine is mechanically blocked or jammed.
E15Overvoltage 过压The supply voltage is above the set upper limit.Check that the voltage upper limit is set correctly, then measure whether the actual supply voltage exceeds it.
E16Undervoltage 欠压The supply voltage is below the set lower limit.Check that the voltage lower limit is set correctly, then measure whether the actual supply voltage falls below it.
E19Motor overtemperature 电机过热The motor temperature signal exceeds the set value, normally from a PTC or thermistor input.Check whether the motor is genuinely overheating, verify the PTC circuit is connected, and allow the motor to cool before restarting.
E20External input failure 外部输入故障A digital input configured as an external fault has been triggered.Check which external device is wired to the fault input and whether it is signalling a fault.
No code matches that search. Send it to us and we will identify it.

The codes you will see most often

These are the codes that come up in first-line support on this series. Each entry explains what is actually happening, not just what the code stands for.

E01 Main power supply out of phase

What triggers it. One phase of the incoming three-phase supply is missing during start or while running.

What to do. Check that the three-phase supply is present and reliable at the input terminals.

E02 Machine overheating

What triggers it. The heatsink temperature has exceeded its limit, normally from poor ventilation, a blocked radiator, a start frequency that is too high, or a control supply that sags during start.

What to do. Confirm the starter is mounted vertically with clear airflow. Check the cooling fan and radiator. Reduce the start frequency. Measure the control power supply voltage under load.

E03 Starting timeout

What triggers it. The motor did not complete the start within the allowed ramp time, usually because the parameter set does not match the motor, or the current limit is too low.

What to do. Review each working parameter against the motor nameplate. If the start fails repeatedly, raise the current limiting multiple.

E05 Motor running overcurrent

What triggers it. The load is drawing more current than the set limit while running.

What to do. Check whether the three-phase voltage is too low, which reduces motor output. Check the driven load for mechanical overload.

E06 Electronic thermal overload

What triggers it. The running current has stayed above the motor rated current long enough for the thermal model to trip.

What to do. Check for sustained overload. Confirm the motor rated current parameter matches the nameplate.

How to read and clear the code

Reading it off the unit

The LED display shows the E-code and the LCD shows the fault name. The starter keeps the last 20 faults; 11.02 is the most recent.

Clearing it

After clearing the underlying cause, press and hold STOP for more than 4 seconds to return the unit to the ready-to-start state.

Numbering note

Codes use an E prefix on the LED display. The manual states 19 protection functions but the error code table defines 17 codes: E09, E17 and E18 are not assigned.