AES-UH LFP lithium battery system cabinet for medium and high power UPS and IDC data center, 51.2V 12C high-rate, up to 102.4kWh per cabinet, RAL9004

AES-UH Data Center LFP Lithium Battery Cabinet for IDC UPS (1–12 C, up to 102.4 kWh)

AES-UH IDC Series(High-rate / Standard / Long-delay)
Energy Capacity
25.6 – 102.4 kWh per cabinet
DC Bus Voltage
204.8 / 256 / 409.6 / 512 V DC
Chemistry / C-rate
LiFePO4 (LFP) · 1 C / 2 C / 4 C / 12 C discharge
Cycle Life
5,000 cycles @ 50% DoD
UPS Compatibility
Drop-in VRLA lead-acid replacement for mainstream medium and high-power IDC UPS
Communication
CAN / RS485 / Dry contact

Lead Time: 7 – 15 days | Shipping: Worldwide (sea / air / express) | Warranty: 2.5 years full machine

IEC 62619IEC 62133UL 1642UN38.3

Excerpt

The AES-UH IDC is a modular LiFePO4 (LFP) lithium battery cabinet designed as a drop-in replacement for VRLA lead-acid batteries in medium and high-power IDC UPS systems. It delivers 1–12 C high-rate discharge for bridge-to-generator events, scales from 25.6 to 102.4 kWh per cabinet, and is rated for 5,000 cycles at 50% depth of discharge. Standard interfaces include CAN, RS485 and dry contact, compatible with major UPS brands without firmware redesign. The RAL9004 cabinet is available in 600×850×2000 and 600×1000×2000 mm footprints, with output voltages of 204.8, 256, 409.6 and 512 V DC. Best suited for data centers, government, finance, telecommunications, medical, education and internet facilities where short backup time and 24/7 reliability matter. Module-level fire suppression and three-tier BMS provide comprehensive protection against overcharge, over-discharge, over-temperature and short circuit.

Key Features

✓

Deliver 12 C High-Rate Discharge for Data Center Bridge-to-Generator

The 51.2 V / 50 Ah high-rate module outputs up to 30.72 kW to protect IDC server racks during 5–15 second bridge-to-generator transfers.

✓

Scale up to 102.4 kWh in RAL9004 IDC Cabinets

Pre-assembled cabinets from 25.6 to 102.4 kWh cover 5-minute to multi-hour backup in 600×850×2000 / 600×1000×2000 mm footprints.

✓

Reach 5,000 Cycles at 50% Depth of Discharge

LFP prismatic cells with adaptive SOC/SOH management deliver 10+ year service life, lowering TCO versus VRLA strings in 24/7 data center operation.

✓

Secure the Pack with Three-Level BMS + Module-Level Fire Suppression

Built-in three-tier BMS provides overcharge, over-discharge, over-temperature, overcurrent and short-circuit protection, with per-module fire extinguishing to stop thermal runaway spread.

✓

Retrofit Mainstream IDC UPS as a Drop-In VRLA Replacement

CAN / RS485 / dry-contact interfaces communicate with leading IDC UPS brands, replacing existing lead-acid strings without UPS firmware or DC bus redesign.

✓

Cover 204.8–512 V DC IDC Bus Standards

Available output voltages include 204.8, 256, 409.6 and 512 V DC, matching the DC bus requirements of most medium and high-power data center UPS systems.

Technical Specifications

Module Configuration

ProjectHigh-rateStandardLong-delay
Rated Capacity (Ah)505075100100100100200
Cell TypeLithium iron phosphate battery (LFP)
Rated Voltage (V)51.251.23225.63225.651.251.2
Discharge Rate (C)124444421
Charge Rate (C)1
Maximum Capacity (kWh)2.562.562.401.923.202.565.1210.24
Output Power (kW)30.7210.249.607.6812.8010.2410.2410.24
Size W×D×H (mm)200×660×175200×570×175200×660×165200×660×165440×440×131440×768×131
Weight (kg)32±228±225±234±230±2—43±280±2

Lithium Battery System Cabinet

Maximum Battery Energy (kWh)25.6 / 38.4 / 30.7 / 51.2 / 40.9 / 51.2 / 102.4
Rated Output Voltage (DC)204.8 / 256 / 409.6 / 204.8 / 512 / 256 V DC
Cycle Life5000 cycles @ 50% discharge depth
Communication InterfaceCAN / RS485 / Dry contact
Protective FunctionOvercharge, over-discharge, over-temperature, overcurrent, short circuit, etc.
Operating Temperature0 °C – 40 °C (recommended 20 – 25 °C)
ColorRAL 9004
Cabinet Size W×D×H (mm)600×850×2000 / 600×1000×2000
Self-discharge Rate< 3% per 30 days (ambient 0 – 30 °C)

Note: parameters based on 25 °C environment. Specifications subject to change without notice.

Typical Applications

The AES-UH IDC Series(High-rate / Standard / Long-delay) is engineered for environments where a single power event can stop production or lose revenue. Wherever continuity matters — in data centres, plants, grids and critical sites — it delivers clean, reliable power when you need it most.

Data Centre & Server Room

Data Centre & Server Room

Keeps racks, cooling and network infrastructure online through mains failure, brownouts and switching, with zero transfer time and clean sinewave output.

Telecommunications

Telecommunications

Protects switching, transmission and BTS/edge sites where a dropped call or a down base station means lost revenue.

Industrial Plants

Industrial Plants

Guards PLCs, drives, robots and process lines against grid dips and outages, cutting downtime, scrap and rework.

Oil & Gas

Oil & Gas

Protects DCS, PLC, SCADA, ESD and instrumentation onshore and offshore, where process continuity and personnel safety are non-negotiable.

Petrochemical & Refinery

Petrochemical & Refinery

Shields batch and continuous process control against voltage events that can destabilise reactors and compressors.

Healthcare

Healthcare

Provides clean, uninterrupted power for medical imaging, diagnostics and life-support equipment.

Commercial & Office Buildings

Commercial & Office Buildings

Delivers quiet, reliable backup for lifts, security, HVAC and business-critical office loads.

UPS Lithium Retrofit

UPS Lithium Retrofit

Replaces lead-acid batteries with lithium to double backup per footprint and extend service life beyond 15 years.

Frequently Asked Questions

Q1. What IDC UPS brands is the AES-UH IDC compatible with?

AES-UH IDC is designed as a universal LFP battery cabinet for mainstream medium and high-power IDC online double-conversion UPS. With CAN, RS485 and dry-contact interfaces, it interfaces with major UPS manufacturers; final compatibility is confirmed against the UPS DC bus voltage and protocol during project design.

Q2. Can AES-UH IDC directly replace my existing VRLA lead-acid batteries?

Yes. The cabinet output voltage (204.8 / 256 / 409.6 / 512 V DC) matches standard IDC UPS DC buses, and no UPS firmware redesign is required in most cases. A site survey is recommended to confirm breaker rating and cable sizing.

Q3. What backup time does AES-UH IDC deliver?

The family covers 5-minute to multi-hour backup, from 25.6 kWh cabinets up to 102.4 kWh. The 12 C high-rate variant is for short bridge-to-generator events; the 1 C long-delay variant is for extended autonomy. Exact runtime depends on UPS load, cabinet kWh and DC bus configuration.

Q4. What is the cycle life and expected service life?

LFP cells are rated at 5,000 cycles at 50% depth of discharge (25 °C reference). With the built-in three-level BMS and adaptive SOC/SOH management, the system is designed for 10+ year service life, typically longer than VRLA replacement intervals in 24/7 data center operation.

Q5. How is the battery protected against fire?

Standard configuration includes module-level fire suppression; cabinet-level fire protection is optional. The three-level BMS provides overcharge, over-discharge, over-temperature, overcurrent and short-circuit protection, with real-time monitoring and fault location.

Q6. What communication and monitoring options are available?

Standard interfaces are CAN bus, RS485 and dry contact. The BMS supports real-time online monitoring, adaptive SOC estimation and life-cycle SOH management, integrable with the UPS monitor or a site DCIM/BMS platform.

Q7. What is the maximum energy from one cabinet?

Up to 102.4 kWh in a 600×1000×2000 mm RAL9004 cabinet. Configurations from 25.6 kWh are available, and multiple cabinets can be paralleled for larger energy needs.

Q8. Is this product suitable for data center IDC applications?

Yes. AES-UH IDC is designed for medium and high-power UPS in government, finance, power, transportation, communication, medical, education and internet industries. The 12 C high-rate variant is especially suited for bridge-to-generator duty where short backup time is critical for IT loads.

Q9. Who should I contact for this UPS — the factory or Brigoind?

Please contact Brigoind. We are the authorized distributor & engineering partner for AVIC-TECH power systems outside China.
What you receive is far more than a UPS unit — it is a full project delivery package, including load calculation, system sizing, single-line diagram design, battery runtime calculation, tender document preparation, lead-time confirmation, export packaging, ocean freight arrangement and customs documentation.
The UPS equipment is manufactured at AVIC-TECH’s factory in China. Every unit comes with factory test reports and relevant product certification documents, and is covered under AVIC-TECH’s official warranty.
Brigoind handles your project communications from initial inquiry through on-site commissioning guidance with multi-language support.
We coordinate after-sales support aligned with your local time zone.
For urgent inquiries, reach us via WhatsApp: +86 135 9996 3955.

Related Products

Why Brigoid

15+
Years Manufacturing
60+
Export Countries
2,000+
Projects Delivered
24/7
Technical Support