Low-voltage Soft Starter

CMC-LX Fault Codes — 11 Alarm Codes and How to Clear Them

The CMC-LX built-in bypass soft starter shows Er-prefixed fault codes on its display, Er01 through Er11, and each one maps to a Modbus code that you can read over RS-485. Two additional display states, STOP and no display, are operating conditions rather than faults and are listed separately. Because the bypass contactor is internal, several codes on this series point at wiring between the starter output and the motor.

11 codes
CodeFaultCauseWhat to do
Er010x01Phase loss when the motor starts 电机起动缺相One phase of the three-phase supply is missing when the motor starts.Measure the voltage of each phase of the three-phase supply and identify which phase is deficient.
Er020x02Thyristor overheat 可控硅过热The heatsink has overheated, normally from poor ventilation, a blocked radiator, a high start frequency, or a control supply that sags during start.Confirm the installation is well ventilated and vertical. Check the heatsink and the overheat protection switch. Reduce the start frequency. Check the control power supply voltage under load.
Er030x03Start failure 起动失败The start did not complete within the time set by parameter L109, usually because the parameter set does not match the motor or the current limit is too small.Check each working parameter against the motor nameplate, and verify the current limiting multiple is not set too low.
Er040x04SCR fault or input-output short circuit 可控硅故障或输入输出短路The input and output of the starter are shorted, or a thyristor has failed. This code also appears when L106 is set to 1.Check the starter output is correctly and reliably connected to the motor. Check the motor for an internal open circuit. Test the thyristors for breakdown. Check the incoming line for phase loss.
Er050x05Current limiting failure or running overcurrent 限流功能失效或运行过流Either the current limiting function is not working as configured, or the motor is drawing too much current in operation.Check whether parameter L100 is set correctly. Check the starter output terminal for short circuit. Check whether the load increased suddenly or fluctuates too much.
Er060x06Electronic thermal overload 电子热过载The thermal model has tripped on sustained overload.Check whether the operation is genuinely overloaded and whether the motor rated current parameter matches the nameplate.
Er070x07Wrong phase sequence 相序错误The incoming line phase order is reversed.Check the incoming phase sequence, and check whether parameter L107 is set correctly.
Er080x08Phase current imbalance 相电流不平衡The three phase currents or voltages are unequal.Check whether the current or voltage in the main circuit is balanced, and whether parameter L103 is set correctly.
Er090x09Frequency failure 频率故障The supply frequency is outside the accepted range.Measure the three-phase input frequency, and check whether parameter L108 is set correctly.
Er100x0AParameter loss 参数丢失The stored parameter set has been erased.If the code returns after re-powering, contact the manufacturer.
Er110x0BWiring error 接线错误The wiring does not match the configured connection mode.Check the wiring against the diagram, and check whether parameter L110 is set correctly.
No code matches that search. Send it to us and we will identify it.

The codes you will see most often

These are the codes that come up in first-line support on this series. Each entry explains what is actually happening, not just what the code stands for.

Er01 Phase loss when the motor starts

What triggers it. One phase of the three-phase supply is missing when the motor starts.

What to do. Measure the voltage of each phase of the three-phase supply and identify which phase is deficient.

Er02 Thyristor overheat

What triggers it. The heatsink has overheated, normally from poor ventilation, a blocked radiator, a high start frequency, or a control supply that sags during start.

What to do. Confirm the installation is well ventilated and vertical. Check the heatsink and the overheat protection switch. Reduce the start frequency. Check the control power supply voltage under load.

Er03 Start failure

What triggers it. The start did not complete within the time set by parameter L109, usually because the parameter set does not match the motor or the current limit is too small.

What to do. Check each working parameter against the motor nameplate, and verify the current limiting multiple is not set too low.

Er05 Current limiting failure or running overcurrent

What triggers it. Either the current limiting function is not working as configured, or the motor is drawing too much current in operation.

What to do. Check whether parameter L100 is set correctly. Check the starter output terminal for short circuit. Check whether the load increased suddenly or fluctuates too much.

Er06 Electronic thermal overload

What triggers it. The thermal model has tripped on sustained overload.

What to do. Check whether the operation is genuinely overloaded and whether the motor rated current parameter matches the nameplate.

Display states that are not fault codes

These two display states are operating conditions rather than protection trips. Check them first before chasing a fault code.

STOP The motor does not work. Check whether terminals X1/3 and X/5 are short-circuited. Check the control circuit wiring and the control switch. Check the control power supply voltage. Verify parameter L200.
No display Nothing on the display. Check whether terminals X1/11 and X1/12 are connected. Check whether the control power supply is normal.

How to read and clear the code

Reading it off the unit

The display shows Er codes. The same fault is also available as a Modbus code (0x01-0x0B) over RS-485.

Clearing it

After clearing the cause, press and hold STOP for more than 2 seconds to return the starter to the ready-to-start state.

Numbering note

Faults are shown on the display as Er01 to Er11. Each fault also has a Modbus communication code (0x01 to 0x0B) for reading over RS-485.