Pump VFD 380-480 V for 1.5-450 kW Motors – XFC500 Series with Built-in PID
XFC500 is a general-purpose 3-phase VFD for fans, water pumps and general automation loads, covering 1.5 kW to 450 kW in 27 ratings with dual G (general duty) and P (fan and pump duty) load types. It combines sensorless vector (SVC) and V/F control on a high-performance DSP platform, with 0.3 Hz / 150% starting torque and a 1:200 speed range. A built-in PID gives constant-pressure water supply control, and dedicated sleep and wake-up functions stop the drive at low load and restart it automatically when pressure drops – a proven energy saver for pumping stations. The XFC500 accepts 380-480 V three-phase input, is IP20 rated, and includes RS485 Modbus RTU as standard.
Key Features
- High-precision motor parameter auto-tuning for accurate vector control
- Sensorless vector (SVC) and V/F control with selectable N-power V/F curves for fan and pump loads
- Built-in PID with sleep and wake-up functions for constant-pressure water supply
- Four sets of motor parameters for multi-pump duty and quick motor changeover
- Stable overvoltage and overcurrent stall control plus fast current limiting, reducing fault trips
- Instantaneous power-failure protection
- G/P dual load ratings: 150% for 60 s / 180% for 3 s (G), 120% for 60 s / 150% for 3 s (P)
- Built-in braking unit up to 22 kW (braking resistor only); 30 kW and above accept an external braking unit
- Built-in DC reactors on models of 132 kW and above
- Common DC bus and DC power supply supported
- Detachable LED keypad with parameter copy function
Technical Specifications at a Glance
| VOLTAGE & PHASE | 3-phase, AC380V-480V, -15%/+10% |
| CURRENT | 4A-822A (27 ratings, rated output current) |
| CONTROL | SVC (Open-loop Vector) / V/F |
| POWER | 1.5-450 kW |
| OVERLOAD | Type G: 150% for 60s / 180% for 3s; Type P: 120% for 60s / 150% for 3s |
| COMMUNICATION | RS485 Modbus RTU; optional CANopen / Profibus-DP / EtherCAT / PLC cards |
| IP | IP20 |
| Output frequency | 0-500 Hz |
| Carrier frequency | 0.5-16 kHz |
| Ambient temperature | -10 to +40 °C (derate 1.5% per 1 °C above 40 °C, up to 50 °C) |
Model Selection: 27 Ratings from 1.5 kW to 450 kW
Each XFC500 rating carries a G (general duty) and a P (fan and pump duty) power value. Select by your motor nameplate data – the drive must be chosen by rated output current, not by catalogue power alone.

| Model | Motor power (kW) | Rated input capacity (kVA) | Rated input current (A) | Rated output current (A) |
|---|---|---|---|---|
| XFC500-3P4-1K50G | 1.5G | 3.2 | 4.8 | 4 |
| XFC500-3P4-2K20G | 2.2G | 4.5 | 6.8 | 5.6 |
| XFC500-3P4-4K00G | 4G | 7.9 | 12 | 9.7 |
| XFC500-3P4-5K50G/7K50P | 5.5G / 7.5P | 11 / 14 | 16 / 21 | 13 / 17 |
| XFC500-3P4-7K50G/11K0P | 7.5G / 11P | 14 / 20 | 21 / 30 | 17 / 25 |
| XFC500-3P4-11K0G/15K0P | 11G / 15P | 20 / 27 | 30 / 41 | 25 / 33 |
| XFC500-3P4-15K0G/18K5P | 15G / 18.5P | 27 / 33 | 41 / 50 | 33 / 40 |
| XFC500-3P4-18K5G/22K0P | 18.5G / 22P | 33 / 38 | 50 / 57 | 40 / 45 |
| XFC500-3P4-22K0G/30K0P | 22G / 30P | 38 / 51 | 57 / 77 | 45 / 61 |
| XFC500-3P4-30K0G/37K0P | 30G / 37P | 51 / 62 | 77 / 94 | 61 / 74 |
| XFC500-3P4-37K0G/45K0P | 37G / 45P | 62 / 75 | 94 / 114 | 74 / 90 |
| XFC500-3P4-45K0G/55K0P | 45G / 55P | 75 / 91 | 114 / 138 | 90 / 109 |
| XFC500-3P4-55K0G/75K0P | 55G / 75P | 91 / 123 | 138 / 187 | 109 / 147 |
| XFC500-3P4-75K0G/90K0P | 75G / 90P | 123 / 147 | 187 / 223 | 147 / 176 |
| XFC500-3P4-90K0G/110KP | 90G / 110P | 147 / 179 | 223 / 271 | 176 / 211 |
| XFC500-3P4-110KG/132KP | 110G / 132P | 179 / 200 | 271 / 303 | 211 / 253 |
| XFC500-3P4-132KG/160KP | 132G / 160P | 167 / 201 | 253 / 306 | 253 / 303 |
| XFC500-3P4-160KG/185KP | 160G / 185P | 201 / 233 | 306 / 353 | 303 / 350 |
| XFC500-3P4-185KG/200KP | 185G / 200P | 233 / 250 | 353 / 380 | 350 / 378 |
| XFC500-3P4-200KG/220KP | 200G / 220P | 250 / 275 | 380 / 418 | 378 / 416 |
| XFC500-3P4-220KG/250KP | 220G / 250P | 275 / 312 | 418 / 474 | 416 / 467 |
| XFC500-3P4-250KG/280KP | 250G / 280P | 312 / 350 | 474 / 531 | 467 / 522 |
| XFC500-3P4-280KG/315KP | 280G / 315P | 350 / 393 | 531 / 597 | 522 / 588 |
| XFC500-3P4-315KG/355KP | 315G / 355P | 393 / 441 | 597 / 669 | 588 / 659 |
| XFC500-3P4-355KG/400KP | 355G / 400P | 441 / 489 | 669 / 743 | 659 / 732 |
| XFC500-3P4-400KG/450KP | 400G / 450P | 489 / 550 | 743 / 835 | 732 / 822 |
| XFC500-3P4-450KG | 450G | 550 | 835 | 822 |
Model code explanation: XFC500-3P4-5K50G-BEN-20 = XFC500 series; 3P4 = three-phase 400 V class (380-480 V); 5K50G = 5.5 kW general duty (7K50P = 7.5 kW fan/pump duty); B = built-in braking unit; E = LED keypad; N = no output reactor (L = with reactor); 2 = IP20; 0 = standard design.
Vector Control and V/F Performance
The XFC500 offers open-loop vector (SVC) and V/F control. In SVC mode it delivers 150% starting torque at 0.3 Hz, a speed range of 1:200 and ±0.5% steady-state speed accuracy. High-precision motor parameter auto-tuning ensures accurate vector control without an encoder. For fan and pump loads, selectable N-power V/F curves (n = 1.2, 1.4, 1.6, 1.8, 2.0) match the drive’s output to the quadratic torque-speed characteristic of centrifugal loads, reducing motor heating and improving energy efficiency.
Built-in PID for Constant Pressure Water Supply
A built-in PID controller (F5 parameter group) closes the process loop directly inside the drive: connect a pressure transmitter to the analog input, set the target pressure, and the drive regulates pump speed to hold pressure constant. This is the standard solution for constant-pressure water supply, booster stations, irrigation systems and HVAC water loops – no external PID controller or PLC is required for the basic loop.
Sleep and Wake-up for Water Pump Applications
For pumping duty, the F6 extended parameters provide sleep and wake-up control: when the set frequency falls to the sleep frequency (F6-00) for the sleep delay time (F6-01), the drive stops automatically; when the demand returns and the set frequency reaches the wake-up frequency (F6-02), the drive restarts after the wake-up delay (F6-03). The pump runs only when water is actually needed, saving energy in low-demand periods such as night hours.
Overload Capacity and Stall Control
Overload capacity follows the load type: G-type ratings provide 150% rated current for 60 s and 180% for 3 s; P-type ratings provide 120% for 60 s and 150% for 3 s. Stable overvoltage and overcurrent stall control and a fast current-limiting function prevent fault shutdowns from frequent current or voltage peaks – important for water systems with sudden load changes.
Multi-pump Control with Four Sets of Motor Parameters
Four sets of motor parameters (C1-C4) allow one XFC500 to drive up to four motors switched through digital inputs – convenient for multi-pump stations that rotate duty and standby pumps without adding a second drive.
I/O Terminals and Expansion Cards
Standard I/O: 5 digital inputs (one supports 100 kHz pulse input), 2 analog inputs (0-10 V / 0-20 mA, jumper selectable), 2 open-collector digital outputs (one supports 100 kHz square-wave output), 1 analog output and 1 relay output (1 NO + 1 NC). An expansion interface accepts the XFC5-IOC-00 IO card (adds 5 DI, 1 AI, 1 relay output, 1 open-collector output and 1 analog output with a CAN interface) and the XFC5-PLC-00 programmable card, which combines PLC + VFD and is compatible with the Mitsubishi PLC programming environment.
RS485 Modbus RTU and Fieldbus Options
RS485 Modbus RTU is built in (F7 group: baud rate up to 38400 bps for Modbus, slave address 1-249 with 0 as broadcast, response delay 0-20 ms). Fieldbus expansion cards add CANopen (XFC5-CAN-00), Profibus-DP (XFC5-PFB-00) and EtherCAT, letting the drive join a plant-wide control network for remote start/stop, speed setting and full parameter readback.
How to Select the Right XFC500 Rating
- Read the motor nameplate: rated power, current, voltage and frequency.
- Choose the load type – G (general duty) or P (fan and pump duty) – matching the application and required overload.
- Select the rating whose rated output current equals or exceeds the motor rated current.
- For fan/pump duty with constant-pressure control, confirm the built-in PID and sleep/wake-up settings.
- Check braking needs: up to 22 kW add a braking resistor; 30 kW and above use an external braking unit.
- Check network requirements and add a fieldbus expansion card if needed.
Applications
The XFC500 is used in constant-pressure water supply, booster and irrigation pumping, HVAC chilled and hot water loops, fans and ventilation systems, compressors, conveyors, mixers and general machinery where reliable variable-speed motor control is required.
FAQ
What is the difference between a VFD and a soft starter?
A VFD varies the motor speed continuously and saves energy on fans and pumps, while a soft starter only ramps the motor up and down at full speed for fixed-speed duty. If the application must run at a fixed speed, a soft starter such as the smart XST260 series or the heavy duty CT series is the lower-cost option; if speed control or energy saving is required, choose a VFD such as the XFC500.
What is the difference between the XFC500 and the XFC550?
The XFC500 is the general-purpose series for fans, pumps and common automation loads, with SVC and V/F control and a built-in PID. The XFC550 adds closed-loop vector (FOC) control, higher torque at zero speed and 180% overload for 3 s for demanding machine applications. For water and HVAC duty, the XFC500 covers the requirement at a better price point.
Which motors can the XFC500 drive?
Standard squirrel-cage asynchronous motors from 1.5 kW to 450 kW (G-type ratings), with a 1:200 speed range in SVC mode. It does not require an encoder, so no speed feedback device is needed for most applications.
Does the XFC500 include a braking function?
Models up to 22 kW include a built-in braking unit as standard – connect a braking resistor only. Models of 30 kW and above require an external braking unit plus braking resistor, selected from the manual’s recommendation table.
Can the XFC500 be used for constant-pressure water supply?
Yes. The built-in PID closes the pressure loop with a transmitter on the analog input, and the sleep/wake-up functions stop the pump in low-demand periods and restart it automatically when pressure drops.
What communication protocols are supported?
RS485 Modbus RTU is standard. Optional expansion cards add CANopen, Profibus-DP, EtherCAT, an IO expansion card and a PLC programmable card.
What is the IP rating and where can it be installed?
The XFC500 is IP20 rated, for indoor installation in a cabinet or wall-mount position with proper clearance. Operating temperature is -10 to +40 °C (derate above 40 °C), humidity below 95% RH (no condensation), and no derating below 1000 m altitude.
What protection functions are built in?
Input and output phase loss, overvoltage, undervoltage, overheat, overload, overcurrent, short circuit, voltage and current limiting, fast current limiting, and a complete fault code table (Err01 inverter protection, Err02-Err04 overcurrent, Err05-Err07 overvoltage, Err09 undervoltage, Err11 motor overload, Err12 input phase loss, Err13 output phase loss, and more) for fast troubleshooting.