Low-voltage Soft Starter
XICHI CT Fault Codes — 19 Alarm Codes and How to Clear Them
The XICHI CT heavy duty soft starter shows faults as two-digit codes on the LCD, from 01 to 19. This series is built for crushers, mixers and conveyors, so overload and starting-timeout codes are far more common here than on a pump starter. The table below gives the cause and the clearing method for each code, with the parameter numbers printed in the original manual.
| Code | Fault | Cause | What to do |
|---|---|---|---|
| 01 | Phase loss of main power 主电源缺相 | A phase is missing on the incoming supply during start or while running. | Check the three-phase supply is present and reliable at the input terminals. |
| 02 | Phase sequence error 相序错误 | The three phase conductors are connected in reverse order. | Correct the phase sequence of the incoming supply, or set parameter B09 so the starter does not check phase sequence. |
| 03 | Loss of parameter 参数丢失 | The stored parameter settings have been lost. | Review each function setting and re-enter the parameters. |
| 04 | Overload protection 过载保护 | The current stays too high for a sustained period, so the motor thermal model trips. | Find and correct the cause of the overload. Check whether the current limiting multiple is too low, whether the starting time is too long, whether the motor overload protection level is reasonable, and whether the motor rated current is set correctly. |
| 05 | Operation overcurrent 运行过流 | The load increased suddenly, or load fluctuation is too large. | Adjust the load operating conditions, and check whether parameter B03 is set too low. |
| 06 | Underload protection 欠载保护 | The motor operating current is below the rated current by more than the underload threshold. | Find the cause of the underload, and check that the settings match the actual operating conditions. |
| 07 | Phase current imbalance 相电流不平衡 | The three phase currents are unequal. | Check whether the imbalance exceeds the level set in parameter B01, then adjust the load running status. |
| 08 | Overvoltage protection 过压保护 | The main circuit voltage is too high. | Measure the main circuit voltage, and check whether overvoltage protection value Q24 is set correctly. |
| 09 | Undervoltage protection 欠压保护 | The main circuit voltage is too low. | Measure the main circuit voltage, and check whether undervoltage protection value Q26 is set correctly. |
| 10 | Phase voltage imbalance 相电压不平衡 | The three phase voltages of the supply are unequal. | Check whether the three-phase voltage of the main circuit is imbalanced, and whether voltage imbalance protection value Q23 is set correctly. |
| 11 | SCR abnormal 晶闸管异常 | A thyristor is short-circuited or not switching correctly. | Test the thyristors for short circuit. If one is damaged, the power module must be replaced. |
| 12 | Leakage lockout 漏电闭锁 | Earth leakage on the load side has exceeded the limit. | Check the grounding insulation of the three-phase winding before re-energising. |
| 13 | Start timeout 起动超时 | The starting time is longer than the permitted limit. | Check whether the current-limiting multiple is too small, and whether the starting time limit parameter B12 is set too low. |
| 14 | Thyristor overheating 晶闸管过热 | The internal heatsink is overheating, usually because the machine is poorly ventilated or the fan has failed. | Confirm the cooling fan is working, reduce the starting frequency, and check whether the control power supply voltage is too low. |
| 15 | Motor temperature 电机温度 | The PTC thermistor inside the motor has detected an over-temperature. | Check that the PTC loop is closed and the input is connected, find and correct the cause of the overheating, and let the motor cool before restarting. |
| 16 | Frequent start 起动频繁 | The starting frequency exceeds the configured starting interval. | Increase the interval between starts, or raise the starting interval parameter Q09 if the duty cycle requires it. |
| 17 | Frequency fault 频率故障 | The supply frequency is outside the accepted range. | Measure the supply frequency and correct it if it is outside the rated range. |
| 18 | Zero sequence protection 零序保护 | Three-phase leakage current exceeds the design value. | Check whether the three-phase leakage exceeds the design value and inspect the load side insulation. |
| 19 | Inching timeout 点动超时 | The inching (jog) time is longer than the permitted limit. | Check the inching time against the inching time limit parameter B13. |
The codes you will see most often
These are the codes that come up in first-line support on this series. Each entry explains what is actually happening, not just what the code stands for.
01 Phase loss of main power
What triggers it. A phase is missing on the incoming supply during start or while running.
What to do. Check the three-phase supply is present and reliable at the input terminals.
04 Overload protection
What triggers it. The current stays too high for a sustained period, so the motor thermal model trips.
What to do. Find and correct the cause of the overload. Check whether the current limiting multiple is too low, whether the starting time is too long, whether the motor overload protection level is reasonable, and whether the motor rated current is set correctly.
05 Operation overcurrent
What triggers it. The load increased suddenly, or load fluctuation is too large.
What to do. Adjust the load operating conditions, and check whether parameter B03 is set too low.
13 Start timeout
What triggers it. The starting time is longer than the permitted limit.
What to do. Check whether the current-limiting multiple is too small, and whether the starting time limit parameter B12 is set too low.
14 Thyristor overheating
What triggers it. The internal heatsink is overheating, usually because the machine is poorly ventilated or the fan has failed.
What to do. Confirm the cooling fan is working, reduce the starting frequency, and check whether the control power supply voltage is too low.
16 Frequent start
What triggers it. The starting frequency exceeds the configured starting interval.
What to do. Increase the interval between starts, or raise the starting interval parameter Q09 if the duty cycle requires it.
How to read and clear the code
Reading it off the unit
A yellow LED lights when a fault is logged, and the LCD shows the two-digit code with the fault name.
Clearing it
After clearing the cause, reset the starter from the keypad. The fault history is retained so you can review the sequence of events.
Numbering note
Codes are shown as plain two-digit numbers (01-19) on the LCD. A yellow LED indicates that a fault has been logged.
Not sure what the display is showing?
Send us a photo of the display together with the model number, and we will identify the code for you. Most replies go out within one business day.
Send your fault code