Low-voltage Soft Starter

CMC-MX Fault Codes — 12 Alarm Codes and How to Clear Them

The CMC-MX Modbus soft starter shows Er-prefixed faults on its display, Er01 through Er13, with Er09 unassigned. Because this model is the Modbus variant with a built-in bypass, several codes point at the internal contactor and at the RS-485 side rather than at the main circuit. STOP and no display are operating states, not faults, and are listed separately below.

12 codes
CodeFaultCauseWhat to do
Er01Phase loss when the motor starts 电机起动缺相One phase is missing on the supply when the motor starts.Measure each phase voltage of the three-phase supply and eliminate the phase loss.
Er02SCR overheating 可控硅过热The heatsink is overheating, normally from poor ventilation, a blocked radiator, a high start frequency, or a control supply that sags during start.Check the ventilation and vertical mounting. Check the heatsink and overheat protection switch. Reduce the start frequency. Check the control power supply voltage under load.
Er03Starting failure 起动失败The start did not complete within the time set by C109, usually because parameters do not match the motor or the current limit is too small.Check each working parameter against the motor nameplate, and verify the current limiting factor is not set too small.
Er04Input-output short circuit or open motor circuit 输入输出短路或电机回路开路Either the input and output of the starter are shorted, or the motor connecting wire is open. The second case applies when C106 is set to 0.Check whether the internal contactor is stuck closed, test the SCR for breakdown, check that the output is correctly connected to the motor, and check the incoming line for phase loss.
Er05Current limiting failure or running overcurrent 限流失效或运行过流Either the current limiting function is not working, or the motor draws too much current in operation.Check whether parameter C100 is set correctly, check the output end for short circuit, and check whether the load increased suddenly or fluctuates too much.
Er06Electronic thermal overload 电子热过载The thermal model has tripped on sustained overload.Check for overload running and verify the motor rated current setting.
Er07Phase sequence error 相序错误The incoming line phase order is reversed.Check the incoming phase sequence and whether parameter C107 is set correctly.
Er08Phase current imbalance 相电流不平衡The main circuit current or voltage is unbalanced.Check whether the main circuit current or voltage is balanced, and check parameter C103.
Er10Parameter loss 参数丢失The stored parameter set has been erased.If the code returns after re-energising, contact the manufacturer.
Er11Wiring error 接线错误The wiring does not match the configured connection mode.Check the wiring against the diagram, and check whether parameter C110 is set correctly.
Er12Internal fault 内部故障An internal fault has been detected, or the main circuit input and output are shorted.Re-energise the control power supply once. Check whether the main circuit input and output terminals are shorted. If the code persists, contact the manufacturer.
Er13Current underload 电流欠载The load has dropped out of the power system.Check whether the load is detached from the power system, for example a broken coupling or a dry pump.
No code matches that search. Send it to us and we will identify it.

The codes you will see most often

These are the codes that come up in first-line support on this series. Each entry explains what is actually happening, not just what the code stands for.

Er01 Phase loss when the motor starts

What triggers it. One phase is missing on the supply when the motor starts.

What to do. Measure each phase voltage of the three-phase supply and eliminate the phase loss.

Er02 SCR overheating

What triggers it. The heatsink is overheating, normally from poor ventilation, a blocked radiator, a high start frequency, or a control supply that sags during start.

What to do. Check the ventilation and vertical mounting. Check the heatsink and overheat protection switch. Reduce the start frequency. Check the control power supply voltage under load.

Er03 Starting failure

What triggers it. The start did not complete within the time set by C109, usually because parameters do not match the motor or the current limit is too small.

What to do. Check each working parameter against the motor nameplate, and verify the current limiting factor is not set too small.

Er05 Current limiting failure or running overcurrent

What triggers it. Either the current limiting function is not working, or the motor draws too much current in operation.

What to do. Check whether parameter C100 is set correctly, check the output end for short circuit, and check whether the load increased suddenly or fluctuates too much.

Er06 Electronic thermal overload

What triggers it. The thermal model has tripped on sustained overload.

What to do. Check for overload running and verify the motor rated current setting.

Display states that are not fault codes

These two display states are operating conditions rather than protection trips. Check them first before chasing a fault code.

STOP The motor does not respond when the start signal is given. Check whether terminals 3 and 5 of X1 are connected. Check the control circuit wiring and the control switch. Check the control power supply voltage. Verify parameter C200.
No display Nothing on the display. Check whether terminals 6 and 7 of X3 are connected. Check whether the control power supply is normal.

How to read and clear the code

Reading it off the unit

The display shows Er codes. Because this is the Modbus variant, the fault can also be read remotely over RS-485.

Clearing it

After clearing the cause, press and hold STOP for more than 4 seconds, or pulse the external fault-clearing input on the D1 multi-function terminal.

Numbering note

Faults are shown as Er01 to Er13. Er09 is not assigned in the official fault table. Two further display states, STOP and no display, are operating conditions rather than faults.

Not sure what the display is showing?

Send us a photo of the display together with the model number, and we will identify the code for you. Most replies go out within one business day.

Send your fault code