Low-voltage VFD

XFC550 Fault Codes — 35 Alarm Codes and How to Clear Them

The XFC550 vector control VFD reports faults as Err codes on the operating panel, from Err01 to Err51 with gaps in the numbering. Unlike a soft starter, most trips on a VFD are about the load dynamics: acceleration and deceleration ramps that are too short, a motor that is still rotating when the drive starts, or a brake unit that is missing where the application needs one. The table below covers all 36 defined codes.

35 codes
CodeFaultCauseWhat to do
Err01Inverter unit protection1. Output circuit shorted. 2. Motor and drive wiring too long. 3. Module overheated. 4. Internal wiring loose. 5. Main control board abnormal. 6. Drive board abnormal. 7. Inverter module abnormal.1. Remove peripheral faults. 2. Install a reactor or output filter. 3. Check that the air duct is clear and the fan is working. 4. Re-seat all cables. 5-7. Contact factory service.
Err02Acceleration overcurrent1. Output circuit grounded or shorted. 2. Vector control without motor parameter tuning. 3. Acceleration time too short. 4. Manual torque boost or V/F curve unsuitable. 5. Supply voltage low. 6. Starting a motor that is already rotating. 7. Sudden loading during acceleration. 8. Drive rating too small for the load.1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Increase the acceleration time. 4. Adjust manual boost or the V/F curve. 5. Bring the voltage into range. 6. Use speed-tracking restart, or wait for the motor to stop. 7. Remove the sudden load. 8. Select a larger drive.
Err03Deceleration overcurrent1. Output circuit grounded or shorted. 2. Vector control without parameter tuning. 3. Deceleration time too short. 4. Supply voltage low. 5. Sudden loading during deceleration. 6. No brake unit or brake resistor installed.1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Increase the deceleration time. 4. Bring the voltage into range. 5. Remove the sudden load. 6. Install a brake unit and resistor.
Err04Constant speed overcurrent1. Output circuit grounded or shorted. 2. Vector control without parameter tuning. 3. Supply voltage low. 4. Sudden loading during running. 5. Drive rating too small for the load.1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Bring the voltage into range. 4. Remove the sudden load. 5. Select a larger drive.
Err05Acceleration overvoltage1. Input voltage too high. 2. Motor driven by an external force during acceleration. 3. Acceleration time too short. 4. No brake unit or brake resistor installed.1. Bring the voltage into range. 2. Remove the external force and install a brake resistor. 3. Increase the acceleration time. 4. Install a brake unit and resistor.
Err06Deceleration overvoltage1. Input voltage too high. 2. Motor driven by an external force during deceleration. 3. Deceleration time too short. 4. No brake unit or brake resistor installed.1. Bring the voltage into range. 2. Remove the external force and install a brake resistor. 3. Increase the deceleration time. 4. Install a brake unit and resistor.
Err07Constant speed overvoltage1. Input voltage too high. 2. Motor driven by an external force during running.1. Bring the voltage into range. 2. Remove the external force and install a brake resistor.
Err08Control power supply faultThe input voltage is outside the range specified for the drive.Bring the supply voltage into the specified range.
Err09Undervoltage fault1. Instantaneous power loss. 2. Input voltage outside the specified range. 3. DC bus voltage abnormal. 4. Rectifier bridge or buffer resistor abnormal. 5. Drive board abnormal. 6. Control board abnormal.1. Reset the fault. 2. Bring the voltage into range. 3-6. Contact factory service.
Err10Frequency converter overloaded1. Load too large or motor stalled. 2. Drive rating too small for the load.1. Reduce the load and check the motor condition. 2. Select a larger drive.
Err11Motor overloaded1. Motor protection parameter F8-03 set incorrectly. 2. Load too large or motor stalled. 3. Drive rating too small.1. Set F8-03 to match the motor nameplate. 2. Reduce the load and check the motor. 3. Select a larger drive.
Err12Input phase loss1. Three-phase input abnormal. 2. Drive board abnormal. 3. Surge protection board abnormal. 4. Main control board abnormal.1. Check the incoming supply and peripheral lines. 2-4. Contact factory service.
Err13Output phase loss1. Lead from drive to motor abnormal. 2. Three-phase output unbalanced while running. 3. Drive board abnormal. 4. Module abnormal.1. Remove peripheral faults. 2. Check the motor three-phase winding. 3-4. Contact factory service.
Err14Module overheated1. Ambient temperature too high. 2. Air duct blocked. 3. Fan damaged. 4. Module thermistor damaged. 5. Inverter module damaged.1. Reduce the ambient temperature. 2. Clean the air duct. 3. Replace the fan. 4. Replace the thermistor. 5. Replace the inverter module.
Err15External equipment fault1. External fault signal received on a multi-function DI terminal. 2. External fault signal received through the virtual IO function.1-2. Clear the external fault, then reset and run.
Err16Communication failure1. Host computer working abnormally. 2. Communication line abnormal. 3. Communication expansion card type parameter U0-00 incorrect. 4. Communication parameters in group F7 incorrect.1. Check the host computer wiring. 2. Check the communication cable. 3. Set the expansion card type correctly. 4. Set the F7 communication parameters correctly.
Err17Contactor failure1. Drive board or power supply abnormal. 2. Contactor abnormal.1. Replace the drive board or power supply board. 2. Replace the contactor.
Err18Current detection fault1. Hall element abnormal. 2. Drive board abnormal.1. Replace the Hall element. 2. Replace the drive board.
Err19Motor tuning fault1. Motor parameters not set from the nameplate. 2. Parameter tuning timed out.1. Set the motor parameters from the nameplate. 2. Check the lead from the drive to the motor.
Err20Encoder fault1. Encoder type does not match. 2. Encoder connection error. 3. Encoder damaged. 4. PG card abnormal.1. Set the encoder type to match the hardware. 2. Fix the wiring. 3. Replace the encoder. 4. Replace the PG card.
Err21EEPROM read/write faultEEPROM chip damaged.Replace the main control board.
Err22Hardware fault of frequency converter1. Overvoltage. 2. Overcurrent.1. Treat as an overvoltage fault. 2. Treat as an overcurrent fault.
Err23Short circuit to groundMotor or output cable shorted to ground.Measure the insulation of the motor and output cable with a megger. Replace the cable or motor.
Err26Total runtime reachedThe total run time counter has reached the set value.Use the parameter initialization function to clear the recorded runtime information.
Err27User-defined fault 1Fault 1 signal received on a multi-function DI terminal or through the virtual IO function.Clear the external condition, then reset and run.
Err28User-defined fault 2Fault 2 signal received on a multi-function DI terminal or through the virtual IO function.Clear the external condition, then reset and run.
Err29Total power-on time reachedThe total power-on time counter has reached the set value.Use the parameter initialization function to clear the recorded information.
Err30Load drop faultThe running current is below the value set in F8-62.Check whether the load has dropped out, and whether F8-62 and F8-63 match the actual operating conditions.
Err31PID feedback lost during runningThe PID feedback is below the value set in F5-26.Check the PID feedback signal, or set F5-26 to a suitable value.
Err40Wave-by-wave current limiting fault1. Load too large or motor stalled. 2. Drive rating too small.1. Reduce the load and check the motor. 2. Select a drive with a larger rating.
Err41Motor switching during operationThe motor selection was changed through a terminal while the drive was running.Perform motor switching only after the drive has stopped.
Err42Speed deviation too large1. Encoder parameter set incorrectly (when C1-61 = 1). 2. Motor stalled. 3. Speed deviation detection parameters F8-67 and F8-68 set improperly. 4. Wiring from drive output UVW to motor abnormal.1. Set the encoder parameters correctly. 2. Check the machine and whether torque setting C1-48 is too small. 3. Set F8-67 and F8-68 reasonably. 4. Check the drive-to-motor wiring.
Err43Motor overspeed1. Encoder parameter set incorrectly. 2. No motor parameter tuning performed. 3. Overspeed detection parameters F8-65 and F8-66 set improperly.1. Set the encoder parameters correctly. 2. Perform motor parameter tuning. 3. Set the detection parameters according to the actual application.
Err45Motor over temperature1. Temperature sensor wiring loose. 2. Motor temperature too high.1. Check the sensor wiring. 2. Reduce the carrier frequency or improve motor cooling.
Err51Initial position errorMotor parameters differ significantly from the actual motor.Confirm the motor parameters are correct, and check whether the rated current is set too small.
No code matches that search. Send it to us and we will identify it.

The codes you will see most often

These are the codes that come up in first-line support on this series. Each entry explains what is actually happening, not just what the code stands for.

Err01 Inverter unit protection

What triggers it. 1. Output circuit shorted. 2. Motor and drive wiring too long. 3. Module overheated. 4. Internal wiring loose. 5. Main control board abnormal. 6. Drive board abnormal. 7. Inverter module abnormal.

What to do. 1. Remove peripheral faults. 2. Install a reactor or output filter. 3. Check that the air duct is clear and the fan is working. 4. Re-seat all cables. 5-7. Contact factory service.

Err02 Acceleration overcurrent

What triggers it. 1. Output circuit grounded or shorted. 2. Vector control without motor parameter tuning. 3. Acceleration time too short. 4. Manual torque boost or V/F curve unsuitable. 5. Supply voltage low. 6. Starting a motor that is already rotating. 7. Sudden loading during acceleration. 8. Drive rating too small for the load.

What to do. 1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Increase the acceleration time. 4. Adjust manual boost or the V/F curve. 5. Bring the voltage into range. 6. Use speed-tracking restart, or wait for the motor to stop. 7. Remove the sudden load. 8. Select a larger drive.

Err03 Deceleration overcurrent

What triggers it. 1. Output circuit grounded or shorted. 2. Vector control without parameter tuning. 3. Deceleration time too short. 4. Supply voltage low. 5. Sudden loading during deceleration. 6. No brake unit or brake resistor installed.

What to do. 1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Increase the deceleration time. 4. Bring the voltage into range. 5. Remove the sudden load. 6. Install a brake unit and resistor.

Err04 Constant speed overcurrent

What triggers it. 1. Output circuit grounded or shorted. 2. Vector control without parameter tuning. 3. Supply voltage low. 4. Sudden loading during running. 5. Drive rating too small for the load.

What to do. 1. Remove peripheral faults. 2. Perform motor parameter tuning. 3. Bring the voltage into range. 4. Remove the sudden load. 5. Select a larger drive.

Err05 Acceleration overvoltage

What triggers it. 1. Input voltage too high. 2. Motor driven by an external force during acceleration. 3. Acceleration time too short. 4. No brake unit or brake resistor installed.

What to do. 1. Bring the voltage into range. 2. Remove the external force and install a brake resistor. 3. Increase the acceleration time. 4. Install a brake unit and resistor.

Err06 Deceleration overvoltage

What triggers it. 1. Input voltage too high. 2. Motor driven by an external force during deceleration. 3. Deceleration time too short. 4. No brake unit or brake resistor installed.

What to do. 1. Bring the voltage into range. 2. Remove the external force and install a brake resistor. 3. Increase the deceleration time. 4. Install a brake unit and resistor.

How to read and clear the code

Reading it off the unit

The operating panel shows the Err code. The drive keeps a fault history that can be reviewed from the panel menu.

Clearing it

Clear the fault from the operating panel after the cause is removed. For faults that persist after reset, the manual points to the drive board or main control board and recommends factory service.

Numbering note

Faults are shown as Err codes on the operating panel, Err01 through Err51 with gaps. Codes Err24, Err25 and Err32-Err39 are not assigned in the official table.

Common symptoms without a fault code

Beyond the numbered codes, the manual documents nine recurring field situations that do not always produce an Err code. They are listed separately because in practice they are what most first-line support calls are about.

SymptomCauseWhat to do
No display after power on1. Grid has no voltage or voltage too low. 2. Switching power supply on the drive board failed. 3. Rectifier bridge damaged. 4. Buffer resistor damaged. 5. Control board or keypad failed. 6. Wiring between control board, drive board and keypad broken.1. Check the input power supply. 2. Check the bus voltage. 3. Re-seat the keypad ribbon. 4-6. Contact factory service.
Shows Err23 immediately after power on1. Motor or output line shorted to ground. 2. Drive damaged.1. Measure the insulation of the motor and output line with a megger. 2. Contact factory service.
Reports Err14 (module overheat) repeatedly1. Carrier frequency set too high. 2. Fan damaged or air duct blocked. 3. Internal components damaged.1. Reduce the carrier frequency (C0-03). 2. Replace the fan and clean the air duct. 3. Contact factory service.
Motor does not rotate when the drive runs1. Motor or motor cable fault. 2. Motor parameters set wrong. 3. Poor contact between drive board and control board. 4. Drive board failed.1. Reconfirm the drive-to-motor connection. 2. Reset the motor parameters or remove the mechanical fault. 3-4. Contact factory service.
DI terminal not responding1. Parameter setting wrong. 2. External signal error. 3. OP +24V jumper loose. 4. Control board failed.1. Check and reset the F1 group parameters. 2. Reconnect the external signal line. 3. Reconfirm the OP +24V jumper. 4. Contact factory service.
Motor speed cannot increase in closed-loop vector control1. Encoder failed. 2. Encoder wired wrong or poor contact. 3. PG card failed. 4. Drive board failed.1. Replace the encoder and reconfirm the connection. 2. Replace the PG card. 3-4. Contact factory service.
Frequent overcurrent and overvoltage faults1. Motor parameters set wrong. 2. Acceleration and deceleration times unsuitable. 3. Load fluctuation.1. Reset the motor parameters or perform motor tuning. 2. Set suitable accel and decel times. 3. Contact factory service if the fluctuation persists.
Err17 at power on or at runSoft start contactor not picking up.1. Check whether the contactor cable is loose. 2. Check whether the contactor is faulty. 3. Check the contactor 24 V supply. 4. Contact factory service.
Power-on display shows 8.8.8.8.8Components on the control board are damaged.Replace the control board.

Not sure what the display is showing?

Send us a photo of the display together with the model number, and we will identify the code for you. Most replies go out within one business day.